Isolation Measurer - PCE-IT413 for high voltage up to 5000V - PCE Instruments
For high voltage up to 5000 V for PCE-IT413 or up to 10,000 V for PCE-IT414For high voltage up to 5000 V (PCE-IT413) or 10 000 V (PCE-IT414) The PCE-IT413 and PCE-IT414 insulation meters are part of a series of highly accurate and robust test instruments with a 6-digit display. This insulation meter has been specially designed for use in the field and under difficult measuring conditions. The device has the advantage of an integrated protective circuit to avoid measurement errors due to leakage currents. It is equipped with a CMOS microprocessor and has an acoustic and optical alarm signal. You are able to work with test voltages of 5 kV or 10 kV (PCE-IT414 only). The range up to 10 kV of the PCE-IT414 model makes it a device with excellent value for money. You are therefore able to perform effective insulation measurements even at high voltage installations. The isolation gauge was calibrated in the factory for high precision digital measurements (recorded in an EEPROM circuit).
Definition of isolation resistance: This is the resistance in ohms of electrical installations. It is therefore of paramount importance for the protection of people from electric shocks and for the prevention of material damage due to uncontrolled fault currents. The state of insulation is controlled and evaluated using insulation measurements. Here you will find an overview of all insulation measuring devices.
Control voltage up to 5000 V (PCE-IT413) and 10,000 V (PCE-IT414)
Security IEC-1010-1 / CAT III / IEC-1010-1 / EN 61010-1
LCD Screen Automatic shutdown after 5 minutes of inactivity
Optional: ISO calibration certificate
DELIVERY
1 x PCE-IT413 or PCE-ITE414 isolation gauge
1 x set test cable
1 x Touch tip with high voltage isolation
8 x AAA batteries
1 x User manual
SPECIFICATIONS
PCE-IT413
Control voltage |
500 V / 1000 V / 2500 V / 5000 V |
Range of measurement |
30 GΩ / 500 V |
|
60 GΩ / 1000 V |
|
150 GΩ / 2500 V |
|
300 GΩ / 5000 V
|
Accuracy |
±5 % |
Output power |
Max. 1 W |
Case isolation resistance |
2000 MΩ / 2000 V |
Static tension between the circuit and the carcass |
700 V AC for max. 1 minute |
AC Alarm Circuit |
For voltages ♣ 450 V AC |
Screen |
LCD |
Operational Altitude |
Max. 2000 m |
Food |
8 x 1.5 V batteries, type AA |
Automatic shutdown |
After 5 minutes of inactivity |
Operational conditions |
0 ... 40 oC / |
Dimensions |
250 x 110 x 190 mm |
Weight |
1.5 kg |
Level of contamination |
2 |