Power analyzer - PCE-830-1 - 3-phase ammeter - PCE Instruments
3-phase ammeter, energy meter and harmonics meter with memory, PC port and software The ammeter allows measurements, from one to three phases, of electrical parameters in alternating current networks.
In addition to the usual parameters such as voltage, current, frequency, power and energy, this amperometer is capable of measuring harmonics, inter-harmonics and asymmetries according to the specifications of EN50160. The amperemeter can detect network defects such as interruptions, intrusions, temporal or transient overtensions (from 16μs of duration) and measure the corresponding values. The LCD point matrix screen with retro lighting and high contrast is able to show up to 35 parameters at the same time. You can connect up to 3 current clamps simultaneously. In the data recorder mode, it can store up to 17470 measurements (3 phases/4 drivers), and in simpler situations, up to 52400 measurements (1 phase/2 drivers), divided into 85 registers. All this allows the PCE-830 amplifier to be used optimally for long-term analysis. The measured values obtained can be sent to the computer at will and processed with the corresponding analysis software.
The scope of delivery contains everything you need to carry out measurements and analyzes (software and data cable included). Although the ammeter is delivered factory calibrated, it can optionally be calibrated in the laboratory and certified according to ISO regulations (during the first order for annual recalibration)
- Network analysis at: 3 phases/4 drivers, 3 phases/3 drivers, 1 phase/2 drivers, 1 phase/3 drivers
- Measuring actual value (V 123 e I 123 )
- Active power measurement (W, KW, MW, GW)
- Apparent and reactive power measurement (KVA, KVAR) - Power factor (PF), phase angle (Φ)
- Energy and work measurement (Wh, KWh, KVARh, PFh)
- Current measurements from 0.1 mA to 3000 A
- Large screen that shows up to 35 parameters simultaneously (3P4W [=3 phases/4 conducteurs])
- CT conditions (1 to 600) and PT (1 to 3000) programmable
- Indication of superimposed current and voltage waveforms
- 512 KB memory with programmable register intervals (measuring share from 2 to 3000 sec., 17470 values using 3 phase/4 conductor system)
- Indication of waveforms, output parameters and harmonic distortions
- Large LCD screen with illuminated dot matrix - Average power (AD in W, KW, MW)
- Maximum power (MD in W, KW, MW) with programmable period
- Analysis of harmonic distortions up to order 99 of curvature
- On-screen indication of up to 50º harmonic waveform
- Indication of maximum value waveform (1024 measurement values / periods)
- Analysis of absolute distortions (%THD-F)
- Graphical balance diagram with 3-phase system parameters
- Detection of up to 28 transients (time and cycles) at programmable threshold (%)
- 3-phase voltage or asymmetric current (VUR)
- 3 voltage or asymmetric current factor (d0%, d2%)
- USB port optically isolated
- Integrated data register timer and schedule
DELIVERY CONTENT
1 x PCE-830 Ammeter
3 x Ampermetric pins according to the set PCE-6801
4 x Insulated socket terminals
4 x 3m safety check line
8 x Piles
1 x Power Adapter
1 x Mallette
1 x USB Cable for PC
1 x Software (English)
1 x Instructions for use
SPECIFICATIONS
Measurement values
|
Measuring ranges / resolution / precision
|
Watts AC (50 o 60 Hz, PF 0.5 to 1)
|
5,0 ... 999,9 W / 0,1 W / ±1% ±0,8 W 1,000 ... 9,999 kW / 0.001 kW / ±1% ±8 W 10,00 ... 99,99 kW / 0.01 kW / ±1% ±80 W 100.0 ... 999.9 kW / 0.1 kW / ±1% ±0,8 kW 1000 ... 9999 kW / 1 kW / ±1% ±8 kW
|
AC current (50 o 60 Hz, selection of range automatic, TRMS)
|
0.04 A ... 1A / 0.001A / ± 0.5 % ± 0.05 A 0.4 A ... 10.0 A / 0.01 A / ± 0.5 % ± 0.05 A 4 A ... 100.0 A / 0.1 A / ±1.0% ±0.5 A
|
AC voltage (50 o 60 Hz, TRMS)
|
20.0 ... 500.0 V / 0.1 V / ±0.5% ±5 digits (Measurement between phase and neutral) 20.0 ... 600.0 V / 0.1 V / ±0.5 % ±5 digits (Measure between phase and neutral)
|
Harmonic distortions of AC voltage
|
1 ... 20º / 0.1% / ±1.0% 21 ... 49o / 0.1% / 4% of the measurement value ±2.0% 50 ... 99º / 0.1% / 6% of the measured value ±2.0%
|
AC current harmonics in %
|
1 ... 20o / 0.1 % / ±0.2% measurement value ±1.0 % 11 ... 20º / 0.1% / ±2% of measurement value ±1.0% 21 ... 50o (A)/ 0.1% / ±5 % measurement value ±1.0% 21 ... 50o (mA)/ 0.1% / ±10% measurement value ±1.0% 51 ... 99º / 0.1% / ±35% of measurement value ±1.0%
|
Power factor (PF)
|
0.00 ... 1.00 / 0.01 / ±0.04
|
Phase shift angle (Phi)
|
-180° ... 180° / 0.1° / ±1°
|
Total harmonic distortion
|
0,0 ... 20,0 % / 0,1 % / ±1 % 20.0 ... 100% / 0.1% / ±3% of measured value ±5% 100 ... 999.9% / 0.1% / ±10% of measurement value ±10%
|
Maximum voltage and AC current measurement
|
50Hz / 19μS / ±5 % ±30 digits 60Hz / 16µS / ±5 % ±30 digits
|
Measurement of the voltage and current AC peak value
|
1.00 ... 99.99 / 0.01 / ±5% ±30 digits
|
Range frequency in automatic mode
|
45 ... 65 Hz / 0.1 Hz / 0.1 Hz
|
Memory
|
512 kB for 52420 measurement values performing 1-phase/2-conductor measurement
|
Port
|
USB (optically isolated)
|
Software and data cable
|
Both in the scope of delivery, for Windows 2000, XP, ME
|
Ecran
|
Illuminated display, dot matrix LCD
|
Food
|
8 x 1.5 V type AA (Mignon)
|
Dimensions
|
257 x 155 x 57mm
|
Weight
|
1160g
|
Environmental conditions
|
Max. 85% relative humidity / -10 ... 50 ºC
|
Type of protection / regulations
|
IEC 61010, 600 V/CAT III
|
Current clamp PCE-6801 (100A) - Capture of the electrical conductor: diameter of 30mm - Selection of range: manual (1A, 10A, 100A) - Dimensions: 210 x 62 x 36 mm - Weight: 200g
|