3-phase power analyzer and neutral return - PCE-360 - PCE Instruments
The four-pole digital tetrapolar power meter PCE-360 is used to measure the power of one or three phases with a return to the neutral. To do this, its large screen displays up to 10 different measurement values. In manual mode, the power meter can keep 99 values in a direct way. On the other hand, in the data recording mode it is possible to memorize up to 20,000 values. It is therefore perfect for conducting long-term analyses.
The values kept in the device can be transmitted to the PC for its subsequent evaluation. In the delivery you will find everything necessary to achieve measurement and evaluation (as well as software and data cable). The power meter is delivered calibrated from the factory and can have an optional ISO calibration certificate (by ordering or performing the annual recalibration).
In addition, it allows thanks to its software to study harmonics to determine possible return to the network or parasites generated by engines, etc.
Stetrapolar power measurement (3P +N)
Real time with memory
Long-term registration
Study of harmonics with software
Large opening clamp: 40 mm
Large multi parameter screen
RS-232 connection for PC
Optional: ISO calibration certificate
DELIVERY
1 x Power Analyzer PCE-360
4 x Current pins
4 X Crocodile pins
4 x Touch tips
1 x Software
1 x RS-322 cable
8 x 1.5V batteries type AA
1 x SECTOR adapter
1 x Employment Notice
SPECIFICATIONS
Tension |
Range of measurement |
0 ... 999,9 V RMS |
Resolution |
0.1 V |
Accuracy |
± 0.3 % of the value + 10 digits |
|
Current |
Range of measurement |
3 ... 999,9 A |
Resolution |
0.1 A |
Accuracy |
± 0.5 % of the value + 15 digits |
|
Actual power P |
Range of measurement |
0 ... 999,9 kW |
Resolution |
0.1 kW |
Accuracy |
± 1% of the measurement + 20 digits |
|
Actual power S |
Range of measurement |
0 ... 999,9 kVA |
Resolution |
0.1 kVA |
Accuracy |
± 1% of the measurement + 20 digits |
|
Actual power Q |
Range of measurement |
0 ... 999,9 kVar |
Resolution |
0.1 kVar |
Accuracy |
± 1% of the measurement + 20 digits |
|
Power factor |
Range of measurement |
0 ... +1 |
Resolution |
0,001 |
Accuracy |
± 3 digits |
|
PF phase angle |
Range of measurement |
- 90° ... +90° |
Resolution |
0,1 |
Accuracy |
± 3 digits |
|
Frequency measurement (Tension voltage50V) |
Range of measurement |
40... 100 Hz |
Resolution |
0.1 Hz |
Accuracy |
± 0.1% value + 2 digits |
|
Recognition of the giratory field (UL phenomenon50V) |
Actual |
Range of measurement |
0 ... 9999 MWh |
Accuracy |
± 0.1% value + 20 digits |
Related work |
Range of measurement |
0 ... 9999 MVah |
Accuracy |
± 0.1% value + 20 digits |
Work reactivated |
Range of measurement |
0 ... 9999 MVarh |
Accuracy |
± 0.1% value + 20 digits
|