Generator soundproof FERBO FE16000-ST-YW-AVR - Diesel - Three-phase 400V 15.6 kVA (12.5kW) 75 dB(A) - Electric start - SMGW
Water cooling
Super soundproof model 75dB(A)±3 to 7 metres:
Engine coupling / Single switch Engine/alternator coupling with single support with disc joint, based on electric welded steel with anti-vibrator interposition.
Two-part soundproof box made of 20/10 sheet metal, soundproofing material of class 1, inner exhaust, manoeels and hinges, loading of fuel from the outside, mobile coupling hook, industrial paint.
Automatic control panel without source inverter:
Control device for generator with automatic start-up in case of power cut: Possibility of exclusion of network control, for manual groups and/or with remote start-up by contact, Functions OFF / MAN / AUTO / TEST, monitoring, control and protection of the engine, generator, network, inversers, reading of the network electrical parameters (tension), generator (tension, current, power, CosPhi), motor data (battery voltage, D + sensor values or ECU, tachymeter, time meter).
TECHNICAL DONNECTIONS |
Group performance 50 Hz |
PRP |
14 KVA |
LTP |
15.6 kVA |
Power factor |
0.8 |
PRP |
11.2 kW |
LTP |
12.5 kW |
Power single-phase if used individually |
5.2 kVA |
Tension |
400V / 230V |
PRP - Prime Power : It is defined as the maximum power that one generator is able to provide continuously while supplying a variable electric charge variable, when operated for an unlimited number of hours per year under agreed operating conditions and that maintenance intervals and procedures are respected as prescribed by the manufacturer. shall be carried out in accordance with the manufacturer ' s requirements. The average allowable power over 24 hours of operation shall not exceed 70% of the initiation power. A Overload capacity of 10% is available for one hour during a 12-hour operating period. |
LTP - Limited-Time running Power : This is the maximum power available, under the agreed operating conditions, that generator is capable of providing for 500 hours. 500 operating hours per year (not more than 300 for continuous use) with the maintenance intervals and procedures prescribed by manufacturers. maintenance as prescribed by manufacturers. No overload capacity is available. |
Engine |
Builder and model |
YANMAR 3TNV70 |
Tower controller |
mechanical |
Pb startup battery |
12V 55Ah |
Emission level |
No show |
Max power. |
22 Hp |
N. Tours/mn |
3000 |
Number of cylinders |
2 |
Cylinder |
854 cc |
75% consumption |
3.1 L/h |
Alternator |
Builder and model |
LINZ E1X13MD/2 or equivalent |
Synchronous with capacitor control |
± 1% |
Number of poles |
2 |
Heating class |
H |
class insulation stator/rotor |
H |
Degree of protection |
IP21 |
Continuous power |
16 kVA |
Soundproof model |
Capture model |
T43 |
dB to 7 metres |
75 dB (A) ±3 |
Integrated fuel tank |
50 l |
Dimension mm |
1300x700x1000 |
Weight kg |
485 |
Automatic control table without source inverter |
Magnetic circuit breaker |
16 A |
Prise |
ECE 16A 400V 5P |
Control panel without source inverter |
COMAP IL4 AMF 9 |
Automatic battery charger |
2.5 A |
Connection for source inverser |
Standard |
Emergency Stop Bottle |
Standard |