Generator on FERBO chassis FE12000-XT-LE-AVR - Diesel - Three-phase 400V - 11 kVA (8.8 kW) - Kholer Engine Electric start - SMGW
Engine KHOLER KD 425-2 - 954 cc
Electric start system
Chassis model: Single support engine/alternator coupling with valves installed on a welded steel base and anti-vibration supports
AVR : Automatic voltage control, avoids damage to devices
ELECTRICAL TABLE |
Magnetic circuit breaker + different switch |
32A 5P outlet with thermal protection |
16A 3P windscreen with thermal protection |
Voltmeter, start-up keys, amperometer, frequencymeter, hour count, low oil pressure LED, network presence LED |
TECHNICAL DONNECTIONS |
Group performance |
Power in cosfi rescue service 0.8 |
11 KVA |
Cosfi continuous power 0.8 |
10 kVA |
Power in single-phase if used individually |
3.3 kVA |
Tension |
400V / 230V |
Tank capacity |
7 L |
Lead Start Battery |
12V 55Ah |
Dimensions in mm |
1060x620x780 |
Weight kg |
183 |
Engine |
Builder and model |
KHOLER KD 425-2 |
Tower controller |
G1 |
Maximum power |
15.6 Hp |
Number of cylinders |
2 |
Cylinder |
954 cc |
75% consumption |
2.5 L/h |
Alternator |
|
Builder and model |
LINZ E1S1MAS-KE
(or equivalent)
|
AVR |
± 1% |
Number of poles |
2 |
class insulation stator/rotor |
H |
Degree of protection |
IP21 |
Continuous power |
10 kVA |